1.2 What 1910.147 covers — and what it does not

More arguments about lockout/tagout are really arguments about scope. Does this task need a lock? Does this exception apply to us? Is the operator who clears jams covered? The answers are all in 1910.147(a), and they are unusually precise — the standard tells you exactly what it covers, exactly what it excludes, and exactly which narrow activities slip out through an exception.

1 The five industries the standard leaves out

1910.147(a)(1)(ii) lists five categories the standard does not cover. They are worth knowing precisely, because each one is governed somewhere else rather than nowhere at all.

Exclusions from 1910.147 and where those workplaces look instead
Excluded by 1910.147(a)(1)(ii)Governed instead by
(A) Construction and agriculture employment29 CFR 1926 for construction — notably 1926.417 (tagging circuits) and 1926.702(j) (concrete and masonry equipment)
(B) Employment covered by parts 1915, 1917 and 1918The maritime standards: shipyards, marine terminals, longshoring
(C) Installations under the exclusive control of electric utilities for power generation, transmission and distribution29 CFR 1910.269
(D) Exposure to electrical hazards from work on, near or with conductors or equipment in electric-utilization installationsSubpart S, principally 1910.333
(E) Oil and gas well drilling and servicingGeneral duty obligations and industry practice; no dedicated OSHA energy control standard

Exclusion (D) causes the most confusion in a manufacturing plant, because most plants do plenty of electrical work. The line is this: when you are servicing a machine and electricity is one of the energy sources you have to control, you are under 1910.147. When the work itself is electrical work on the utilization installation — pulling a motor starter, working in a panel, terminating a feeder — 1910.333(b)(2) governs, and it adds a requirement 1910.147 does not have: an instrument test of the conductors. Part 3, Chapter 2 and Part 4, Chapter 4 both come back to this.

2 Production versus servicing, and the door between them

1910.147(a)(2)(ii) states that normal production operations are not covered by the standard, and then immediately opens a door: servicing or maintenance that takes place during normal production operations is covered if either of two things is true.

  1. A
    An employee is required to remove or bypass a guard or other safety device; or
  2. B
    An employee is required to place any part of the body into an area on the machine where work is performed on the material being processed (the point of operation), or where an associated danger zone exists during a machine operating cycle.

This is the paragraph that decides the argument about clearing jams, wiping down rollers, picking a dropped part out of a chute, or reaching into a wrapper to free a film. If the hand goes past the guard, or into the point of operation, or into a danger zone that exists during the cycle, the work has walked through the door and 1910.147 applies to it.

On the job: a good test on the floor is to watch where the interlock is defeated. If someone is holding a magnet on a switch, propping a gate, or has learned the timing of a cycle so they can reach in between strokes, you are looking at (a)(2)(ii) work that is being done without energy control.

3 The minor servicing exception, and how it is misused

Attached to (a)(2)(ii) is a note that has probably been stretched further than any other sentence in the standard. It reads: minor tool changes and adjustments, and other minor servicing activities, which take place during normal production operations, are not covered by this standard if they are routine, repetitive, and integral to the use of the equipment for production, provided that the work is performed using alternative measures which provide effective protection.

Four conditions, all of them at once:

Routine
A regular, scheduled part of running the machine
Repetitive
Recurring, not a one-off
Integral
Necessary to keep production going
Alternative protection
Effective protection is actually provided

The fourth condition is the one that gets dropped. "Alternative measures which provide effective protection" means something real: a two-hand control that cannot be tied down, an interlock that cannot be defeated and drops power, a light curtain that stops the cycle, a positively driven guard, a hold-to-run device. It does not mean training, a warning sign, a rule about being careful, or the operator's experience. If the only thing standing between a hand and the point of operation is a decision, the exception has not been met and the machine needs to be locked out.

Common mistake: writing "minor servicing exception" on a task list and stopping there. The exception is a conclusion, not a justification. Whoever claims it should be able to name the alternative measure, show it on the machine, and explain why it is effective for that specific task.

4 Cord-and-plug equipment

1910.147(a)(2)(iii)(A) removes from the standard "work on cord and plug connected electric equipment for which exposure to the hazards of unexpected energization or start up of the equipment is controlled by the unplugging of the equipment from the energy source and by the plug being under the exclusive control of the employee performing the servicing or maintenance."

Two conditions again, and the second is where it usually falls apart. Exclusive control means the plug is in the technician's sight, in their hand, in their pocket, or behind a plug lockout box that only they can open. A cord that disappears behind a machine and plugs into a receptacle on the far side of a wall is not under anyone's exclusive control — someone will plug it back in, and they will be helping.

The first condition matters too: unplugging must control the hazard. A bench grinder unplugged is safe. A cord-connected hydraulic power pack with a charged accumulator is not, because pulling the plug does nothing about the stored energy. In that case the exception does not apply and the full standard does.

5 Hot tap operations

The third exception, 1910.147(a)(2)(iii)(B), covers hot tap operations on pressurized transmission and distribution pipelines carrying gas, steam, water or petroleum products. It is available only where the employer demonstrates three things: that continuity of service is essential, that shutdown of the system is impractical, and that documented procedures are followed and special equipment is used which will provide proven effective protection for employees.

A hot tap is defined at 1910.147(b) as a procedure involving welding on a piece of equipment — pipelines, vessels or tanks — under pressure, in order to install connections or appurtenances. It is specialized work with its own engineering controls, and the exception is written narrowly enough that it cannot be borrowed for ordinary maintenance on a pressurized line. "We could not shut it down without stopping production" is not the same as "shutdown is impractical."

6 Where 1910.147 sits among other standards

1910.147(a)(3)(ii) is a short paragraph with wide consequences: when other standards in part 1910 require the use of lockout or tagout, they shall be used and supplemented by the procedural and training requirements of this section. In other words, 1910.147 is the backbone. When a permit-required confined space entry under 1910.146 calls for isolating a space, or a machine guarding requirement leads to servicing work, the energy control comes back here for its procedures, its devices and its training.

The purpose paragraph, 1910.147(a)(3)(i), states the whole thing in one sentence: the section requires employers to establish a program and use procedures for affixing appropriate lockout or tagout devices to energy isolating devices, and to otherwise disable machines or equipment, to prevent unexpected energization, startup or release of stored energy in order to prevent injury. Program, procedures, devices, and the phrase "otherwise disable" — which is where blocking a suspended ram or chocking a roll comes in.

If you take one thing from this chapter, make it this: scope questions have written answers. Before anyone argues on the floor about whether a task needs a lock, someone should be able to point at (a)(2)(ii), (a)(2)(iii) or the minor servicing note and say which one they are relying on. Most of the time, nobody can — and that is the answer.

Key takeaways
  • 1910.147(a)(1)(ii) excludes construction and agriculture, maritime work, utility generation/transmission/distribution installations, electric-utilization electrical work (subpart S), and oil and gas well drilling and servicing.
  • Servicing during production is covered whenever an employee must remove or bypass a guard, or place part of the body into the point of operation or a danger zone during the cycle (1910.147(a)(2)(ii)(A)-(B)).
  • The minor servicing exception requires all four conditions — routine, repetitive, integral, and alternative measures giving effective protection. The last one is usually the missing one.
  • Cord-and-plug work is exempt only if unplugging controls the hazard and the plug stays under the exclusive control of the person doing the work (1910.147(a)(2)(iii)(A)).
  • Hot tap work is exempt only where continuity of service is essential, shutdown is impractical, and documented procedures with special equipment give proven effective protection (1910.147(a)(2)(iii)(B)).
  • When another 1910 standard calls for lockout or tagout, it is supplemented by the procedures and training of 1910.147 (1910.147(a)(3)(ii)).