Fire Extinguisher Monthly Inspection Log

OSHA requires portable fire extinguishers to be visually inspected monthly, given an annual maintenance check, and hydrostatically tested at the intervals in Table L-1. This log records all three on one sheet: list your units once, and the form works out when each one is next due. Nothing you type is sent to our servers.

1910.157(e)(2): extinguishers are visually inspected monthly. One sheet per month, per area.
This is the decision behind 1910.157(b) and (g). Whichever line you are on, the units still have to be inspected, maintained and tested.

Nothing you type is sent to our servers. A draft is kept in this browser until you clear it.

Template for informational purposes only. This document must be reviewed and adapted by a competent or qualified person for your specific jobsite, equipment, and applicable federal, state, and local requirements. It does not constitute legal, engineering, or safety advice and does not by itself establish compliance with OSHA or any other standard. SteelToeTools assumes no liability for its use. Nothing you type is sent to our servers.

How to use this log

  1. 1
    Build the register once. Walk the area with the sheet blank and write down every unit: ID or serial, where it hangs, what type it is, and the two dates stamped or tagged on it — last annual maintenance and last hydrostatic test. That is the only slow month.
  2. 2
    Let the sheet do the dates. Pick the type from the list and the log applies the Table L-1 interval for you: five years or twelve, plus the six-year internal maintenance date for stored pressure dry chemical units. Next month you print the same sheet with the dates already on it.
  3. 3
    Print it blank and carry it. Leave the register rows and the checkpoints empty and the printed sheet comes out ruled with three boxes per line — a clipboard sheet, not a form you have to fill in twice.
  4. 4
    Fill the alternate protection column. Every unit you send away leaves a gap. 1910.157(e)(5) says that gap has to be covered while the unit is out, and that is the line an inspector reads.
  5. 5
    Keep it with the annual maintenance record. The annual record is the one 1910.157(e)(3) actually requires you to keep. This sheet is how you show the eleven months in between were not blank.

What OSHA requires

29 CFR 1910.157(e)(1) puts the whole thing on the employer: “The employer shall be responsible for the inspection, maintenance and testing of all portable fire extinguishers in the workplace.” Three separate obligations follow, on three separate clocks.

The three clocks on a portable fire extinguisher — 29 CFR 1910.157(e) and (f)
WhatHow oftenRecord required?
Visual inspectionMonthlyNone stated in 1910.157(e)(2)
Maintenance checkAnnual — stored pressure units need no internal examinationYes: the annual maintenance date, kept one year after the last entry or the life of the shell, whichever is less(e)(3)
Internal maintenance, stored pressure dry chemical on a 12-year testEvery 6 years — emptied and maintained; non-refillable disposable containers exemptRestarts from any recharge or hydrostatic test(e)(4)
Hydrostatic test5 or 12 years by type — Table L-1Yes: certification record with the test date, the tester's signature and the unit's serial number(f)(2), (f)(16)

What the monthly inspection covers — and who says so

OSHA never lists the monthly checkpoints. 1910.157(e)(2) is one sentence: portable extinguishers, or the hose used in lieu of them, “shall be visually inspected monthly.” The detailed monthly checklist everyone quotes comes from NFPA 10, a copyrighted consensus standard we name but do not reproduce. The checkpoints on this form are instead the conditions 1910.157 and 1926.150 state in their own text — each one carries the paragraph it comes from.

There is one place where the copyrighted standard is binding anyway, and it is the one most construction employers miss: 1926.150(c)(1)(viii) requires portable fire extinguishers on construction work to be “inspected periodically and maintained in accordance with Maintenance and Use of Portable Fire Extinguishers, NFPA No. 10A-1970” — incorporated by reference, and therefore enforceable. If you run construction work, that edition is the maintenance rule OSHA will hold you to, alongside the monthly inspection of 1910.157(e)(2).

Table L-1 — hydrostatic test intervals

Hydrostatic test intervals, reproduced from Table L-1 of 29 CFR 1910.157(f)(2) (CFR text, public domain)
Type of extinguisherTest interval (years)
Soda acid (stainless steel shell)5
Cartridge operated water and/or antifreeze5
Stored pressure water and/or antifreeze5
Wetting agent5
Foam (stainless steel shell)5
Aqueous Film Forming foam (AFFF)5
Loaded stream5
Dry chemical with stainless steel5
Carbon dioxide5
Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells12
Dry chemical, cartridge or cylinder operated, with mild steel shells12
Halon 121112
Halon 130112
Dry powder, cartridge or cylinder operated with mild steel shells12

Extinguishers with shells of copper or brass joined by soft solder or rivets were to be removed from service by January 1, 1982 and are not hydrostatically tested. OSHA's own eTool notes that soda acid and cartridge operated water and antifreeze units, although still in Table L-1, are obsolete. Wet chemical (Class K) units do not appear in Table L-1 at all: follow the manufacturer's instructions and the applicable fire code.

Five findings that void the interval

1910.157(f)(2) says an extinguisher is tested at the Table L-1 interval except under five conditions — and each of them is something the monthly walk is where you notice:

  • the unit has been repaired by soldering, welding, brazing or a patching compound — (f)(2)(i);
  • the cylinder or shell threads are damaged — (f)(2)(ii);
  • corrosion has caused pitting, including under a removable nameplate assembly — (f)(2)(iii);
  • the extinguisher has been burned in a fire — (f)(2)(iv);
  • a calcium chloride agent has been used in a stainless steel shell — (f)(2)(v).

On top of those, 1910.157(f)(4) requires a hydrostatic test whenever a unit shows new evidence of corrosion or mechanical injury. A shell that fails a test, or is not fit for testing, is removed from service and from the workplace — 1910.157(f)(14).

Two types that come off the wall for good

1910.157(c)(3) prohibits providing or making available any extinguisher using carbon tetrachloride or chlorobromomethane, and 1926.150(c)(1)(vii) repeats the ban for construction. 1910.157(c)(5) requires the employer to remove from service all soldered or riveted shell self-generating soda acid, self-generating foam, or gas cartridge water type units that are operated by inverting the extinguisher. If one of those is still hanging in a plant room, the monthly walk is where it gets found.

This generator produces a template. It does not establish compliance with 1910.157, 1926.150, NFPA 10, your local fire code or your insurer's requirements, and it does not replace the annual maintenance check or the hydrostatic test, both of which are done by trained persons with the proper equipment. The employer remains responsible for the inspection, maintenance and testing of every unit and for the accuracy of this record.

Frequently asked questions

Monthly. 29 CFR 1910.157(e)(2) says portable extinguishers, or the hose used in lieu of them under (d)(3), shall be visually inspected monthly. On top of that, 1910.157(e)(3) requires an annual maintenance check, and 1910.157(f)(2) requires hydrostatic testing at the intervals in Table L-1 — five years or twelve years depending on the type of extinguisher.

No. The standard says the extinguisher shall be visually inspected monthly and stops there. What OSHA does state elsewhere in 1910.157 is the condition the unit has to be in: fully charged and operable, in its designated place, accessible without injury, free of the corrosion and mechanical damage listed in (f)(2) and (f)(4), and not one of the prohibited or withdrawn types in (c)(3) and (c)(5). Every checkpoint on this form comes from one of those paragraphs. NFPA 10 publishes a detailed monthly checklist, and it is a copyrighted consensus standard — we name it rather than copy it.

Not in general industry. 1910.157(e)(3) requires you to record the annual maintenance date and keep that record for one year after the last entry or the life of the shell, whichever is less, and 1910.157(f)(16) requires a hydrostatic test certification record with the test date, the tester's signature and the unit's serial number. The monthly visual inspection has no recordkeeping paragraph attached to it. In construction it is different: 1926.150(c)(1)(viii) requires extinguishers to be inspected periodically and maintained in accordance with NFPA 10A-1970, which OSHA incorporates by reference. Either way, an inspector who asks how you know the monthly check happened will want a sheet like this one.

Table L-1 of 1910.157 sets the interval by type. Five years for stored pressure water and antifreeze, wetting agent, AFFF, loaded stream, dry chemical with a stainless steel shell, and carbon dioxide. Twelve years for stored pressure dry chemical with mild steel, brazed brass or aluminum shells, cartridge or cylinder operated dry chemical and dry powder with mild steel shells, and Halon 1211 and 1301. This log computes the due date from the last test date you enter.

Five conditions in 1910.157(f)(2): the unit has been repaired by soldering, welding, brazing or a patching compound; the cylinder or shell threads are damaged; corrosion has caused pitting, including under a removable nameplate assembly; the extinguisher has been burned in a fire; or a calcium chloride agent has been used in a stainless steel shell. Separately, 1910.157(f)(4) requires a test whenever a unit shows new evidence of corrosion or mechanical injury. Those conditions are checkpoints on this form because the monthly walk is when you find them.

1910.157(e)(4): stored pressure dry chemical extinguishers that require a 12-year hydrostatic test are emptied and put through the applicable maintenance procedures every 6 years. Units with non-refillable disposable containers are exempt, and when the unit is recharged or hydrostatically tested the 6-year clock restarts from that date. The log flags the 6-year date for every unit you record as stored pressure dry chemical.

1910.157(e)(5) requires alternate equivalent protection while a unit is removed for maintenance and recharging — an empty bracket is a gap in the coverage that the spacing rules in 1910.157(d) and 1926.150(c)(1) were laid out to close. This form has a line for it on every deficiency, because that is the step most often skipped.

In general industry, travel distance to a Class A unit is 75 feet or less, 50 feet or less for Class B, and 75 feet or less to a Class D agent — 1910.157(d)(2), (d)(4) and (d)(6). In construction, 1926.150(c)(1)(i) requires a unit rated at least 2A for each 3,000 square feet of protected building area with travel distance no more than 100 feet, one on each floor, one adjacent to the stairway in multistory buildings, and a 10B unit within 50 feet of anywhere more than 5 gallons of flammable or combustible liquid or 5 pounds of flammable gas are in use.